Specifications
System Accuracy
Breaker Mount or Universal with
Internal CTs:
+/-1% of full scale current rating
Universal for External CTs:
+/-1% of full scale current rating plus CT
accuracy
Current Input
Current Range: 1% to 125% of current rating
Burden: 1 VA
Voltage Input
Voltage Range: +/-20% of voltage rating
Frequency
50 or 60 Hertz
Power Factor Range
All (-1 to +1)
Communications
9600 Baud
INCOM compatible
Environmental Conditions
Operating Temperature:
-25° to 70°C ¿
(-13° to 158°F)
Storage Temperature:
-40° to 85°C ¿
(-40° to 185°F)
Operating Humidity:
5% to 95% relative humidity non-condensing
Dimensions DxWxH (inches)
F 3.20 x 4.12 x 1.30; hole clearance* 0.59
J 4.04 x 4.12 x 1.28; hole clearance* 0.77
K 4.04 x 5.31 x 1.25; hole clearance* 0.96
UI 4.36 x 5.31 x 3.00; hole clearance 1.17
UE 4.36 x 5.31 x 3.00
Weight (lbs):
F .65
J .69
K .87
UI 1.10
UE 1.10
General Specifications
Power Requirement
10 VA maximum
Input Voltage
120 or 240 VAC (±20%)
Auto selecting
Frequency
50 or 60 Hz
Operating Temperature
0° to 70°C
(32° to 158°F)
Storage Temperature
- 20° to 85°C
( - 40° to 185°F)
Humidity
5% to 95% R.H. non-condensing
Alarm Contact Ratings
10 A @ 277 VAC (resistive)
10 A @ 30 VAC (resistive)
1/3 HP 125, 250 VAC |
* Hole clearance available for bare cable after stripping insulation.
¿ 40°C (standard) maximum for Series C circuit breakers.
Terminal, Cable and Wiring Guidelines
Energy Sentinel |
Westinghouse Series C TerminaL |
Wire Size (Single Conductor) |
|
F-frame |
624B100G02, G17, G18, G19 |
#14-1/0, #4-4/0, #4-4/01, #14-1/0 AWG |
J-frame |
T250KB, TA250KB |
#4-350 MCM |
K-frame |
T350K, TA350KB |
#250-500 MCM |
Universal
with Internal CTs |
#250-500 MCM |
System Voltage Reference Wiring |
#24-#10 AWG |
Current Transformer Wiring |
#12 AWG (max.) |
Ground Reference Wiring |
#22-#12 AWG (minimum 600V rated) |
Communications Wiring |
Cutler-Hammer IMPCABLE or
Belden 9463 family |
|
Top of Page
Support Services
Product Support
Application Support
Cutler-Hammer sales offices worldwide provide technical assistance in the specification and use of Westinghouse IQ products.
Factory Assistance
Cutler-Hammer provides factory applications and technical assistance to its customers. Available by telephone, Cutler-Hammer personnel quickly respond to customer needs – troubleshooting problems, analyzing system operation, and coordinating component repair or replacement.
Factory assistance may be obtained by calling the Advanced Products Support Center at (800) 809-2772 or (412) 490-6714.
Installation and Startup Services
Cutler-Hammer provides a complete package of retrofitting and startup services, by factory trained engineers and technicians, for Westinghouse or non-Westinghouse equipment.
Additionally, IMPACC startup services include:
Setting addresses.
Troubleshooting the data line.
Loading and configuring the software.
Preparing Custom Graphic screens.
Training operators and programmers.
Training
Cutler-Hammer also provides comprehensive training on IMPACC and IMPACC- compatible devices from its Pittsburgh Training Center. The Training Center also offers on-site training for all of its courses. For more information on training, please call (412) 494-3715.
Further Information
Selling Policy 25-000
User's Manual
F-frame IL 17537
J-frame IL 17538
K-frame IL 17539
Universal Internal IL 17540
Universal External IL 17541
IMPACC Wiring Specification TD 17513
Sales Aid (Commercial) SA 11919
Sales Aid (Industrial) SA 11920
Price List 8174
Discount Symbol C10-S24
UL File No. E64983
CSA File No. LR106359-1
Top of Page
Catalog Information |
IQ Energy Sentinels
Description | Voltage Rating - Vac | Current Rating Max. Amps | Catalog Number |
For F-frame Breakers |
120/240, 240, 208Y/120 |
150 |
IQESF208 |
For F-frame Breakers |
220/380, 230/400, 240/415 |
150 |
IQESF400 |
For F-frame Breakers |
480, 480Y/277 |
150 |
IQESF480 |
For F-frame Breakers |
600, 600Y/347 |
150 |
IQESF600 |
|
For J-frame Breakers |
120/240, 240, 208Y/120 |
250 |
IQESJ208 |
For J-frame Breakers |
220/380, 230/400, 240/415 |
250 |
IQESJ400 |
For J-frame Breakers |
480, 480Y/277 |
250 |
IQESJ480 |
For J-frame Breakers |
600, 600Y/347 |
250 |
IQESJ600 |
|
For K-frame Breakers |
120/240, 240, 208Y/120 |
400 |
IQESK208 |
For K-frame Breakers |
220/380, 230/400, 240/415 |
400 |
IQESK400 |
For K-frame Breakers |
480, 480Y/277 |
400 |
IQESK480 |
For K-frame Breakers |
600, 600Y/347 |
400 |
IQESK600 |
|
Universal with Internal CTs |
120/240, 240, 208Y/120 |
400 |
IQESUI208 |
Universal with Internal CTs |
220/380, 230/400, 240/415 |
400 |
IQESUI400 |
Universal with Internal CTs |
480, 480Y/277 |
400 |
IQESUI480 |
Universal with Internal CTs |
600, 600Y/347 |
400 |
IQESUI600 |
|
Universal for External CTs |
120/240, 240, 208Y/120 |
4000 |
IQESUE208 |
Universal for External CTs |
220/380, 230/400, 240/415 |
4000 |
IQESUE400 |
Universal for External CTs |
480, 480Y/277 |
4000 |
IQESUE480 |
Universal for External CTs |
600, 600Y/347 |
4000 |
IQESUE600 |
|
Top of Page
|