- Select required breaker from the table.
- Determine which trip unit model is required: OPTIM 750; or OPTIM 1050 which provides additional features of power, energy, and harmonics monitoring.
- Determine if LSIA or LSIG with ground fault protection is required.
- Determine breaker frame ampere rating bas-ed on required ampere interrupting capacity.
- Select required rating plug.
- Based on continuous trip rating required. (All rating plugs are fixed.)
- Select required terminals.
- Determine size and number of wires being used for load and line terminations.
- Select enclosure based on required breaker frame size.
- Select neutral if required.
- Neutral is required for three-phase, four-wire wye systems.
- Specify voltage system to be applied.
- For control power transformer primary in the control power unit.
- Select a minimum of one hand held OPTIMizer programmer.
- Required for initializing the address and can be used on multiple systems.
- Select other options as required.
- Breaker Interface Module (BIM) panel mounted user interface.
- INCOM Communications Module allows a BIM to communicate over an IMPACC network to a remote personal computer.
- Ground fault alarm relay unit (GFAU). Used with ground fault option to provide contacts for remote alarming.
- Enter items on Bid Manager for pricing and order entry.