Environmental Conditions
| Operating Temperature: | -20° to 70° C |
| Storage Temperature: | -30° to 85° C |
| Operating Humidity: | 0 to 95% |
| Relative Humidity |
| Device Weight: | 4.7 lbs w/o |
| Power Module |
Current Input (Each Channel)
| Current Range: | 0-40 Amperes AC |
| Nominal Full | |
| Scale Current: | 5 Amperes AC |
| Overload Withstand: | 40 Amperes AC, |
| Continuous |
| 300 Amperes AC, |
| 1 second |
| Input Impedance: | 0.002 ohm |
| Burden: | 0.05 VA |
Voltage Inputs (Each Channel)
| Voltage Range (Nominal): | 0-600 Vac |
| Nominal Full | |
| Scale Voltage: | 120-600 Vac |
| Overload Withstand: | 635 Vac, Continuous |
| 700 Vac, 1 second |
| Input Impedance: | 1 M ohm |
UL/CUL Listed
File Number E62791
This brochure is published solely for information purposes and should not be considered all inclusive. If further information is required, you should consult your nearest Cutler-Hammer salesperson.
| |
Frequency Range
45-66 Hz
Harmonic Response
(Voltages, Currents)
50th Harmonic
Accuracy (percent of Full Scale)
Accuracy maintained from 3-300% of
Full Scale and from -0.5 to 1.00 to 0.5
power factor.
| Current and Voltage: | ±0.20% |
| Power and Energy: | ±0.40% |
| Frequency: | ±0.40% |
| Power Factor: | ±0.80% |
Control Power Input
(Separate Source Power Module Only)
| Input Range, AC: | 96-264 Vac |
| Frequency Range: | 45-66 Hz |
| Input Range, DC: | 100-350 Vdc |
| Burden: | 21 VA |
Discrete Inputs (Dry Contact)
+30 Vdc differential across each discrete
input pair of terminals.
Minimum Pulse Width: 1.6 msec
Optically isolated inputs to protect
IQ Analyzer circuitry.
Analog Outputs
0 to 20mA / 4 to 20mA into max. 1 k ohm load.
Accuracy: 1%.
| |
Analog Input
0 to 20mA / 4 to 20mA into 200 ohm load.
Accuracy: 1%.
Relay Output Contacts
| Form C Dry Contact: | 10 Amperes @
120/240 Vac
(Resistive)
10 Amperes @
30 Vdc
(Resistive)
|
| Minimum Pulse Width: | 4 cycles (68 ms) |
| Withstand Rating: | 1000 Vac, 1 min.
across contacts
5000 Vac
(contacts to coil,
1 min.)
10,000 Vac
(contacts to coil,
surge voltage) |
Relay Response Time
(excluding programmed time delays):
- 2 line cycles for Discrete Input,
IMPACC command
(communications port)
- 4-5 line cycles for Voltage
Disturbance, Voltage Unbalance
- 9-10 line cycles for all others
Fuses
(Supplied with the unit) ¾ Ampere, 600 volts
Buss Type KTK-R-¾ (3 required)
|