ANSI C37.90 (Total Compliance):
(UL Required)
- Make and Carry Ratings Sec. 6.7
- Temperature Test Sec. 7
- Dielectric Test Sec. 8
- Surge Withstand Test Sec. 9
UL 1053 (UL Required):
- Current Withstand Test Sec. 27
- Control Power Test Sec. 18
- Output Test Sec. 19
- Temperature Test Sec. 20
- Calibration of Ground Element Sec. 21
- Overvoltage Sec. 22
- Overload Sec. 23
- Endurance - Verify with Calibration Tests Sec. 24
- Dielectric Voltage Withstand Test Sec. 25
CURRENT INPUTS:
- CT's - 5 Amp Secondary
- CT Burden
<0.004Ohm <0.1VA@Rated Current(5A)
- In - 5A(Secondary) or CT(Primary)
- Saturation - 30 x In
- Momentary - 100 x In for 1 Second
CT(Primary) SETTINGS AVAILABLE:
- Phase and Ground:
5/10/25/50/75/100/150/200/250/300/400/500/600/630
800/1000/1200/1250/1500/1600/2000/2400/2500
3000/3200/4000/5000
ZONE SELECTIVE INTERLOCKS:
- Phase - Inverse Time Overcurrent and Short Delay
- Ground - Inverse Time Overcurrent and Short Delay
CONTROL POWER:
- Input Voltage
Nominal 48 to 250VDC Nominal 120 TO 240vac 50/60Hz
- Input Voltage
Operating Range 28 to 280VDC Operating Range 90 TO 254vac 50/60Hz
- Power Consumption- 25VA
OUTPUT TRIP CONTACTS:
- Trip OC/Communication [Time Delay]
- Make 30 Amps for 0.25 Seconds - 0.25 Amp Break at 250VDC
- Trip Instantaneous
- 5 Amp Break at 120/240VAC
- Communications Close
- Meets ANSI C37.90, Paragraph 6.7
ENVIRONMENT:
- Operating Temperature: -30 to +55 Degrees C
- Operating Humidity: 0 to 95% Relative Humidity [Non-Condensing]
- Storage Temperature: -40 to +70 Degrees C
AUXILIARY ALARM CONTACTS:
- Protection Off Alarm - 5 Amp Continuous
- Trip Alarm - 5 Amp Break at 120/240VAC
TESTS:
- Dielectric Strength
Current Inputs - 3000VAC for 1 Minute Phase-Phase
- Seismic Test
Meets requirements for UBC and California Building Code Zone 4. ZPA=3.5
|
|
ADDITIONAL TESTS (UL REQUIRED):
- Hot and Cold Calibration of Phase Elements
- Meter Readout Accuracy
- Zone Interlocking Functionality
EMC TESTS:
- IEC 255-22-2, Electrostatic Discharge Test (ESD), Rating of 8kV
- IEC 255-22-3, (ENV50140), Radiated RF Immunity
- ENV 50141, Conducted RF Immunity
- CISPR 11 Class A
- CFR 47 FCC Part 15 Subpart b Class A
PHASE AND GROUND TIME-CURRENT CURVES:
- Low Voltage Breaker
It - Moderately Inverse
I2t - Very Inverse
I4t - Extremely Inverse
FLAT - Definite Time
- ANSI(Per ANSI C37.112, 1996)
Moderately Inverse
Extremely Inverse
- IEC (Per IEC 255-3, 1989)
IEC-A - Moderately Inverse
IEC-B - Very Inverse
IEC-C - Extremely Inverse
IEC-D - Definit Time
PHASE OVERCURRENT PICKUP RANGES:
- Inverse Time Overcurrent
Setting: (0.2 to 2.2) x In (28 Settings)
- Short Delay Setting
(1 to 11) x In, None[25 Settings]
- Instantaneous Setting
(1 to 25) x In, None[30 Settings]
GROUND OVERCURRENT PICKUP RANGES:
- Inverse Time Overcurrent
Setting: (0.1 to 2.2) x In None[26 Settings]
- Short Delay Setting
(0.1 to 11) x In, None[45 Settings]
- Instantaneous Setting
(0.5 to 11) x In, None[33 Settings]
TIME DELAY SETTINGS:
- Inverse Time Overcurrent
Time Multiplier: It, I2t, I4t Curve: 0.2 to 40 [47 Settings]
FLAT: 0.2 to 2 [21 Settings]
ANSI(all): 0.1 to 5.0 [50 Settings]
IEC(all): 0.05 to 1.00 [20 Settings]
- Short Delay Time
0.05 to 1.5 Sec. [22 Settings]
CURRENT MONITORING:
- True RMS Sensing
3-Phase and Ground
- Display Accuracy
+/- 1% of Full Scale[In] from 0.04xIn to 1xIn
+/- 2% of Full Scale[In] from 1xIn to 2xIn
- Amp Demand
Average Demand over 5 Minute Sampling Window
- High Load
85% of Inverse Time Overcurrent Setting
TIMING ACCURACY:
- Inverse Time Overcurrent
Time - +/- 10% at >1.25 x Pickup
- Short Delay Time
+/- 50ms
COMMUNICATIONS:
- IMPACC Compatible
- Baud Rate - 1200 or 9600
- Catalog DT3000 has Built-in INCOM, NO PONI REQUIRED!
|