Digitrip3000 Overcurrent Relay

How to Configure the Digitrip3000 as a DigitripMV


Back to Main Digitrip 3000 Product Sheet

The Digitrip3000 can be installed as a direct replacement for the Digitrip MV. The connection and wiring is identical. The DT3000 will function and communicate as a DTMV provided the proper DIP switch settings are configured.

The following five (5) points must be observed for DT3000 operation as a DTMV:

  1. DIP switches S1, S2 and S3 must be set to the off position.
  2. The selected curve shape must be It, I2t, I4t or FLAT.
  3. The phase and ground curves must be set the same.
  4. The CT Settings must be set from the front panel. They can not be set via IMPACC.
  5. Only the Thermal curves are used for system coordination.